Update to South Australian system black restoration.
POWER SYSTEM EVENT
Power is being restored to SA via the Victora to South Australia Heywood interconnector.,
At 1940 hrs the following constraint was applied to the Victoria to South Australia Heywood interconnector.
#V-SA_E
The RHS of this constraint will be varied as required.
Manager NEM Real Time Operations
Update to South Australian system black restoration.
POWER SYSTEM EVENT
At 1618 hrs the SA power system separated from the NEM and became black. A very large lightning storm was traveling across the state at the time. Refer MN# 54994
AT 1813 hrs the restoration is proceeding as per AEMO's restoration plan a connection to Victoria has been restored. As more information becomes available further updates will be sent.
Manager NEM Real Time Operations
AEMO has become aware of the following circumstance(s) with respect to the South Australian power system,
POWER SYSTEM EVENT
AEMO has become aware of the following circumstance(s) with respect to the power system,
At 1618 hrs the SA power system separated from the NEM and became black. A very large lightning storm was traveling across the state at the time.
The exact number of effected transmission elements are unknown at this time.
Approximately 1900MW was shed as part of this incident. All generation and load in SA was lost.
AEMO has initiated its South Australian black start procedures and has begun restoring South Australia from two sources.
AEMO has issued this Market Notice in accordance with the NER Cl 4.8.3.
Manager NEM Real Time Operations
AEMO advises that a Black system condition exists in the South Australia region
Power system emergency-Black system condition
AEMO advises that a Black system condition exists in the South Australia region
Manager NEM Real Time Operations
[EventId:201609222000_NRM_QLD1_NSW1_stopped] NEGRES CONSTRAINT NRM_QLD1_NSW1 ceased operating from 22 September 2016 20:00
Issued by Australian Energy Market Operator Ltd at 2000 hrs on 22 September 2016
CANCELLATION - ACTUAL NEGATIVE SETTLEMENT RESIDUES - QLD to NSW - 22 September 2016.
Refer to market notice: 54947
AEMO has ceased taking action to minimize the further accumulation of negative settlement residues on the QLD to NSW directional interconnector.
The negative residue constraint NRM_QLD1_NSW1 ceased operating at 2000 hrs on 22 September 2016.
This is an AEMO autogenerated Market Notice.
[EventId:201609221840_NRM_QLD1_NSW1_started] NEGRES CONSTRAINT NRM_QLD1_NSW1 started operating from 22 September 2016 18:40
Issued by Australian Energy Market Operator Ltd at 1840 hrs on 22 September 2016
ACTUAL NEGATIVE SETTLEMENT RESIDUES - QLD to NSW - 22 September 2016.
Electricity Market outcomes have resulted in the accumulation of negative settlement residues that have exceeded the allowable negative residue threshold for the QLD to NSW directional interconnector.
The negative residue constraint set NRM_QLD1_NSW1 commenced operating from 1840 hrs on 22 September 2016.
This constraint set contains an equation with the following interconnectors on the LHS:
N-Q-MNSP1
NSW1-QLD1
The RHS of the constraint equation may be adjusted to manage residues.
This is an AEMO autogenerated Market Notice.
Update - Non-credible contingency event - Qld region - 18/09/16
Update - Non-credible contingency event - Qld region - 18/09/16
Update to MN 54932.
At 2135 hrs the Ross 4 Transformer 132 kV CB 4442 was returned to service.
The cause of this non-credible contingency event has been identified and AEMO is satisfied that another occurrence of this event is unlikely under the current circumstances.
AEMO will not reclassify this event as a credible contingency event.
Manager NEM Real Time Operations
Non-credible contingency event - Qld region - 18/09/16
Non-credible contingency event - Qld region - 18/09/16
At 1956 hrs the Ross 4 Transformer 132 kV CB 4442 opened at the 132 kV connection only.
AEMO did not instruct load shedding.
AEMO has not been advised of any disconnection of bulk electrical load.
The cause of this non credible contingency event is not known at this stage.
Refer to AEMO Network Outage Scheduler (NOS) for further details.
Manager NEM Real Time Operations
Non-credible contingency event - Tas Region - 31 July 2016
Non-credible contingency event - Tas Region - 31 July 2016
At 0602 hrs the Farrell - Reece No 1 and the Farrell - Reece No 2 220 kV Lines tripped.
AEMO did not instruct load shedding.
AEMO has not been advised of any disconnection of bulk electrical load.
AEMO will reclassify this event as a credible contingency event due to lightning
Manager NEM Real Time Operations