Update: Forecast Lack Of Reserve Level 1(LOR1) in the South Australia region - STPASA - 6 July 2016
RE: AEMO Electricity Market Notice No. 54173 & 54178.
NOTICE OF UPDATE
AEMO declares a Forecast LOR1 condition for the South Australia region for the following period:
From 06/07/2016 1800 hrs to 2030 hrs
The contingency capacity reserve required is 400 MW.
The minimum reserve available is 296 MW.
Harmohan Singh
Operations Planning
Inter regional transfer limit variation - Hazelwood Rowville No. 3 500 kV line (Vic), Thursday, 30 June 2016
Inter regional transfer limit variation - Hazelwood Rowville No. 3 500 kV line (Vic), Thursday, 30 June 2016
A short notice outage of the Hazelwood Rowville No. 3 500 kV line (Vic) has occurred at 0950 hrs.
Refer to the NOS for details.
The following outage constraint set has be invoked
V-HWRO3
The outage constraint contains the following interconnectors on the LHS
NSW-QLD1
T-V-MNSP1
V-S-MNSP1
V-SA
VIC1-NSW1
Power System Operations Manager
Inter regional transfer limit variation - Hazelwood South Morang No. 1 500 kV line (Vic), Thursday, 30 June 2016
Inter regional transfer limit variation - Hazelwood South Morang No. 1 500 kV line (Vic), Thursday, 30 June 2016
The planned outage of the Hazelwood South Morang No 1 500kV line (Vic) scheduled to finish at 1630 hrs has been returned to service early, at 0950 hrs.
Refer to the NOS for details.
The following outage constraint set has been revoked
V-HWSM at 0950 hrs.
The outage constraint set contains the following interconnectors on the LHS
NSW-QLD1
T-V-MNSP1
V-S-MNSP1
V-SA
VIC1-NSW1
Power System Operations Manager
Update: Forecast Lack Of Reserve Level 1(LOR1) in the South Australia region - STPASA - 4 to 6 July 2016
RE: AEMO Electricity Market Notice No. 54159 & 54172.
NOTICE OF UPDATE
AEMO declares a Forecast LOR1 condition for the South Australia region for the following period(s):
1. From 04/07/2016 1730 hrs to 2130 hrs
The minimum reserve available is 166 MW
2. From 05/07/2016 1830 hrs to 1930 hrs
The minimum reserve available is 378 MW
3. From 06/07/2016 1800 hrs to 2100 hrs
The minimum reserve available is 284 MW
The contingency capacity reserve required over the above periods of forecast LOR1 conditions is 400 MW.
Harmohan Singh
Operations Planning
Update on Heywood Interconnector upgrade
Update on Heywood Interconnector upgrade
Refer to Market Notice 51916
ElectraNet expects to achieve commercial operation of the South East - Tailem Bend 275 kV line series compensation by 31 July 2016. At this time, capability of the Heywood interconnector will be 570 MW for transfer from Victoria to South Australia and 500 MW for transfer from South Australia to Victoria. Further transfer capability will be released subject to completion of inter-network testing to prove system performance and validate system models. System conditions for the conduct of these tests are being obtained through normal market dispatch.
Based on progress with the testing to date, full capability for transfer from Victoria to South Australia is likely to be achieved by February 2017. However, it appears unlikely that the market will deliver sufficient test conditions to enable achievement of full capability for transfer from South Australia to Victoria before March 2017.
If the full range of required conditions are not obtained by July 2017, AEMO and ElectraNet may seek to obtain test facilitation services in order to complete the inter-network tests. This will allow the market approximately 12 months to deliver the required test conditions from when the South East - Tailem Bend series compensation is commissioned.
The inter-network test program for the Heywood interconnector upgrade provides further information and is published on AEMO's website at the following link:
http://www.aemo.com.au/Consultations/National-Electricity-Market/Heywood-interconnector-upgrade-program-for-internetwork-tests
AEMO Operations
Forecast Lack Of Reserve Level 1 (LOR1) in the South Australia region - STPASA - 4-5 July 2016
AEMO declares a Forecast LOR1 condition for the South Australia region for the following period(s):
1. From 04/07/2016 1230 hrs to 2300 hrs
The contingency capacity reserve required is 400 MW
The minimum reserve available is 247 MW
2. From 04/07/2016 2330 hrs to 05/07/2016 0030 hrs
The contingency capacity reserve required is 400 MW
The minimum reserve available is 281 MW
3. From 05/07/2016 1800 hrs to 2030 hrs
The contingency capacity reserve required is 400 MW
The minimum reserve available is 285 MW
Harmohan Singh
Operations Planning
Inter-regional transfer limit variation - Horsham-Waubra 220 kV Transmission Line (Vic)
Inter-regional transfer limit variation - Horsham-Waubra 220 kV Transmission Line (Vic)
The planned outage of the Horsham-Waubra 220 kV Line starting at 0600 hrs has been cancelled.
The following constraint set was associated with this outage.
V-HOWA
The constraint set contains equations with the following interconnectors on the LHS.
NSW-QLD1
VIC1-NSW1
V-SA
V-S-MNSP1
T-V-MNSP1
Manager NEM Real Time Operations
Inter-regional transfer limit variation Lismore SVC - NSW Saturday, 25 June 2016
Inter-regional transfer limit variation Lismore SVC - NSW Saturday, 25 June 2016
At 2320 hrs, there was an unplanned outage of the Lismore SVC.
The following constraint set was invoked from 2325 hrs.
N-LS_VC1
The constraint set contains equations with the following interconnectors on the LHS.
N-Q-MNSP1
NSW1_QLD1
See Network Outage Scheduler (NOS) for further details
Manager NEM Real Time Operations
Inter-regional transfer limit variation - Liverpool - Sydney West No. 30 330 kV Transmission Line (NSW)
Inter-regional transfer limit variation - Liverpool - Sydney West No. 30 330 kV Transmission Line (NSW)
Liverpool - Sydney West No. 30 330 kV Transmission Line has been returned to service early in the NSW region.
The following constraint set was revoked at 0845 hrs.
N-LPSW_30
The constraint set contains equations with the following interconnectors on the LHS.
N-Q-MNSP1
NSW-QLD1
VIC1-NSW1
Refer to AEMO Network Outage Schedule for further details.
Manager NEM Real Time Operations