Planned outage of Heywood to South East No.1 275 kV line in South Australia and Victoria regions from 11/10/2016 0700 hrs to 13/10/2016 1700 hrs
This market notice is FOR INFORMATION ONLY.
The Heywood to South East No.1 275 kV line in South Australia and Victoria regions is planned out of service from 0700 hrs on 11 October 2016 to 1700 hrs on 13 October 2016. During this outage, Heywood 500/275 kV M1 transformer will be off-loaded
During this outage, a credible contingency can separate South Australia region from the rest of the NEM.
Under these circumstances, 35 MW of Raise and Lower regulation FCAS will be sourced from South Australia for the duration of this outage. In addition, consistent with AEMO existing procedures, adequate contingency FCAS lower requirements will also be sourced from South Australia at times when power transfer is from South Australia to Victoria.
The following constraint sets have been invoked for this outage:
F-I-HYSE (includes F-S_LREG_0035 and F-S_RREG_0035)
I-HYSE
S-X_BC_CP
V-HYTX_M12
Refer AEMO Network Outage Schedule (NOS) for further details.
AEMO will continue monitoring this proposed outage and will update the Market accordingly.
Terry Liu
AEMO Operations
Cancellation of the Actual (LOR2) condition in the South Australia region - 10 Sept 2016
Cancellation of the Actual (LOR2) condition in the South Australia region - 10 Sept 2016
Refer to AEMO Electricity Market Notice No. 54886
The Actual LOR2 condition in the South Australia Region is cancelled at 1805 hrs 10 Sept 2016
Manager NEM Real Time Operations
Actual LOR2 South Australia Region - 09 Sept 2016
Actual LOR2 South Australia Region - 09 Sept 2016
Refer AEMO Electricity Market Notice 54872
An Actual LOR2 condition is declared for the South Australia region from 1800 hrs until further notice due to the planned outage of the Heywood No.2 500 kV busbar.
If a credible contingency event occurs during this period the South Australia region would separate from the rest of the NEM and is likely to result in interruptions to power supplies.
There are sufficient capacity reserves in the South Australia region to meet electricity demand but it may not be possible to bring the required additional capacity into service in time to avoid automatic under-frequency load shedding causing power interruptions.
Manager NEM Real Time Operations
Cancellation of the Actual (LOR2) condition in the South Australia region - 09 Sept 2016
Cancellation of the Actual (LOR2) condition in the South Australia region- 09 Sept 2016
Refer to AEMO Electricity Market Notice No. 54882
The Actual LOR2 condition in the South Australia Region is cancelled at 0945 hrs 09 September 2016
Manager NEM Real Time Operations
Actual LOR2 South Australia Region - 09 Sept 2016
Actual LOR2 South Australia Region - 09 Sept 2016
Refer AEMO Electricity Market Notice 54686
An Actual LOR2 condition is declared for the South Australia region from 0710 hrs until further notice due to the planned outage of the Heywood No.2 500 kV busbar.
If a credible contingency event occurs during this period the South Australia region would separate from the rest of the NEM and is likely to result in interruptions to power supplies.
There are sufficient capacity reserves in the South Australia region to meet electricity demand but it may not be possible to bring the required additional capacity into service in time to avoid automatic under-frequency load shedding causing power interruptions.
Manager NEM Real Time Operations
Cancellation of the Actual (LOR2) condition in the South Australia region 09 Sept 2016
Cancellation of the Actual (LOR2) condition in the South Australia region 09 Sept 2016
Refer to AEMO Electricity Market Notice No. 54861
The Actual LOR2 condition in the South Australia Region is cancelled at 0535 hrs 09 September 2016
Manager NEM Real Time Operations
Update - Planned outage of Heywood No.2 500kV Bus in Victoria region
Update to Market Notice 54686 and 54866
This market notice is FOR INFORMATION ONLY.
The current outage of the Heywood No.2 500 kV busbar in Victoria Region had been extended to 1700 hrs on 12 September 2016. The planned end time of this outage has been revised to 1000 hrs on the 11 September 2016.
Please refer to AEMO Network Outage Schedule (NOS) for further details.
During this outage, Heywood 500/275 kV M2 transformer will be off-loaded and Heywood - Mortlake - Alcoa Portland No.2 500 kV line will be opened at Heywood.
During this outage, a credible contingency can separate South Australia region from the rest of the NEM.
Under these circumstances, 35 MW of Raise and Lower regulation FCAS will be sourced from South Australia for the duration of this outage. In addition, consistent with AEMO existing procedures, adequate contingency FCAS lower requirements will also be sourced from South Australia at times when power transfer is from South Australia to Victoria.
The following constraint sets have been invoked for this outage:
F-I_HYSE (includes F-S_LREG_0035 and F-S_RREG_0035)
S-BOTH_BLKRG_C_OS
V-HYTX_M12
V-HY_500BUS
Manager NEM Real Time Operations
Update - Planned outage of Heywood No.2 500kV Bus in Victoria region
Update to Market Notice 54686
This market notice is FOR INFORMATION ONLY.
The current outage of the Heywood No.2 500 kV busbar in Victoria Region has been extended to 1700 hrs on 12 September 2016. Please refer to AEMO Network Outage Schedule (NOS) for further details.
During this outage, Heywood 500/275 kV M2 transformer will be off-loaded and Heywood - Mortlake - Alcoa Portland No.2 500 kV line will be opened at Heywood.
During this outage, a credible contingency can separate South Australia region from the rest of the NEM.
Under these circumstances, 35 MW of Raise and Lower regulation FCAS will be sourced from South Australia for the duration of this outage. In addition, consistent with AEMO existing procedures, adequate contingency FCAS lower requirements will also be sourced from South Australia at times when power transfer is from South Australia to Victoria.
The following constraint sets have been invoked for this outage:
F-I_HYSE (includes F-S_LREG_0035 and F-S_RREG_0035)
S-BOTH_BLKRG_C_OS
V-HYTX_M12
V-HY_500BUS
Manager NEM Real Time Operations
Planned outage of Moorabool to Mortlake PS 500kV line in Victoria region from 16/09/2016 0700 hrs to 16/09/2016 1700 hrs
**Re-scheduled outage from Ausnet. **
Orginally planned for 15/09/2016 0700 hrs to 15/09/2016 1700 hrs and now been rescheduled as below.
This market notice is FOR INFORMATION ONLY.
The Moorabool to Mortlake PS 500kV line in Victoria Region is planned out of service from 0700 hrs on 16 September 2016 to 1700 hrs on 16 September 2016.
During this outage, a credible contingency can separate South Australia region from the rest of the NEM.
Under these circumstances, 35 MW of Raise and Lower regulation FCAS will be sourced from South Australia for the duration of this outage. In addition, consistent with AEMO existing procedures, adequate contingency FCAS lower requirements will also be sourced from South Australia at times when power transfer is from South Australia to Victoria.
The following constraint sets have been invoked for this outage:
F-V-MLMO (includes F-S_LREG_0035 and F-S_RREG_0035)
S-X_BC_CP
V-MLMO
Refer AEMO Network Outage Schedule (NOS) for further details.
AEMO will continue monitoring this proposed outage and will update the Market accordingly.
Edmund Hon
AEMO Operations