Market Notices

53399INTER-REGIONAL TRANSFER17/05/2016 02:57:25 PM

Inter-Regional Transfer Limit Variation - Directlink - NSW Region 17 May 2016

AEMO ELECTRICITY MARKET NOTICE

Inter-Regional Transfer Limit Variation - Directlink - NSW Region - 17 May 2016

The planned outage of the DC2 pole of Directlink was scheduled to complete at 1700 hrs 18/05/16.

The outage has completed early

The following constraint set for this outage was revoked at 1455 hrs.
N-X_MBTE_2

The constraint set contains the following interconnector on the left hand side:
N-Q-MNSP1

See AEMO Network Outage Scheduler (NOS) for further details.

Manager NEM Real Time Operations
53390GENERAL NOTICE17/05/2016 07:28:52 AM

Update to planned outage at Tailem Bend - SA Region 17 May 2016

Update to planned outage at Tailem Bend - SA Region 17 May 2016

There is currently a planned outage of the Tailem Bend 275kV East Bus. Commencing at 0830 hrs 17/05/16, the outage is extended and will also offload the Tailem Bend - Cherry Gardens 275 kV line. During this outage, a trip of the Tailem Bend - Tunkilo 275 kV line severs the 275 kV connections between Victoria and South Australia regions. Should this contingency occur, AEMO will invoke the following FCAS regulation constraint sets.

F-S_LREG_0035
F-S_RREG_0035

For this contingency, the two regions remain connected by the 132 KV network but the next contingency will result in separation of Victoria and South Australia regions.

Refer to AEMO Network Outage Schedule (NOS) for further details

Manager NEM Real Time Operations
53383RECLASSIFY CONTINGENCY17/05/2016 05:43:40 AM

Cancellation of the Reclassification of a Non-Credible Contingency Event: Burnie - Sheffield No.2 110 kV and Sheffield - Paloona - Ulverstone 110 kV Lines in Tasmania due to Lightning.

AEMO ELECTRICITY MARKET NOTICE

Cancellation of the Reclassification of a Non-Credible Contingency Event: Burnie - Sheffield No.2 110 kV and Sheffield - Paloona - Ulverstone 110 kV Lines in Tasmania due to Lightning.

Refer AEMO Electricity Market Notice 53332

There is no longer any lightning activity in the vicinity of the Burnie - Sheffield No.2 110 kV and Sheffield - Paloona - Ulverstone 110 kV Lines.

AEMO has cancelled the reclassification of the simultaneous trip of those circuits as a credible contingency event at 0535hrs.


Manager NEM Real Time Operations
53382RECLASSIFY CONTINGENCY17/05/2016 05:40:33 AM

Cancellation of the Reclassification of a Non-Credible Contingency Event: Norwood - Scottsdale - Derby 110 kV Line and Norwood - Scottsdale 110 kV Line in Tasmania due to Lightning.

AEMO ELECTRICITY MARKET NOTICE

Cancellation of the Reclassification of a Non-Credible Contingency Event: Norwood - Scottsdale - Derby 110 kV Line and Norwood - Scottsdale 110 kV Line in Tasmania due to Lightning.

Refer AEMO Electricity Market Notice 53334

There is no longer any lightning activity in the vicinity of the Norwood - Scottsdale - Derby 110 kV Line and Norwood - Scottsdale 110 kV Line.

AEMO has cancelled the reclassification of the simultaneous trip of those circuits as a credible contingency event at 0535 hrs.


Manager NEM Real Time Operations
53379RECLASSIFY CONTINGENCY17/05/2016 05:37:39 AM

Cancellation of the Reclassification of a Non-Credible Contingency Event: Farrell - Reece No. 1 and No. 2 220 kV Lines in Tasmania due to Lightning.

AEMO ELECTRICITY MARKET NOTICE

Cancellation of the Reclassification of a Non-Credible Contingency Event: Farrell - Reece No. 1 and No. 2 220 kV Lines in Tasmania due to Lightning.

Refer AEMO Electricity Market Notice 53337

There is no longer any lightning activity has ceased in the vicinity of the the Farrell - Reece No. 1 and No. 2 220 kV Lines.

AEMO has cancelled the reclassification of the simultaneous trip of those circuits as a credible contingency event at 0535hrs.

Constraint Sets F-T-FARE_N-2 revoked.


Manager NEM Real Time Operations
53358RECLASSIFY CONTINGENCY17/05/2016 03:00:07 AM

Cancellation of the Reclassification of a Non-Credible Contingency Event: Rowville - Yallourn No.5 & No.6 220 kV Lines in Victoria due to Lightning.

AEMO ELECTRICITY MARKET NOTICE

Cancellation of the Reclassification of a Non-Credible Contingency Event: Rowville - Yallourn No.5 & No.6 220 kV Lines in Victoria due to Lightning.

Refer AEMO Electricity Market Notice 53335

There is no longer any lightning activity in the vicinity of the Rowville - Yallourn No.5 & No.6 220 kV Lines.

AEMO has cancelled the reclassification of the simultaneous trip of those circuits as a credible contingency event at 0300 hrs.

Constraint Set

V-ROYP56_R_N-2 revoked.


Manager NEM Real Time Operations
53343RECLASSIFY CONTINGENCY17/05/2016 12:34:21 AM

Reclassification of a Non-Credible Contingency Event: Farrell - Reece No. 1 and No. 2 220 kV Lines in Tasmania due to Lightning.

AEMO ELECTRICITY MARKET NOTICE

Reclassification of a Non-Credible Contingency Event: Farrell - Reece No. 1 and No. 2 220 kV Lines in Tasmania due to Lightning.

Lightning is occurring near the Farrell- Reece No. 1 and No. 2 220 kV Lines.

AEMO considers the simultaneous trip of those circuits to now be more likely.

Therefore AEMO has reclassified this as a credible contingency event from 0035hrs 17 May 2016 until further notice.

Constraint Set F-T-FARE_N-2 invoked.


Manager NEM Real Time Operations
53336RECLASSIFY CONTINGENCY16/05/2016 11:47:33 PM

Cancellation of the Reclassification of a Non-Credible Contingency Event: Eildon - Mt. Beauty No. 1 and No. 2 220 kV Lines in Victoria due to Lightning.

AEMO ELECTRICITY MARKET NOTICE

Cancellation of the Reclassification of a Non-Credible Contingency Event: Eildon - Mt. Beauty No. 1 and No. 2 220 kV Lines in Victoria due to Lightning.

Refer AEMO Electricity Market Notice 53333

There is no longer any lightning activity in the vicinity of the Eildon - Mt. Beauty No. 1 and No. 2 220 kV Lines.

AEMO has cancelled the reclassification of the simultaneous trip of those circuits as a credible contingency event at 2345hrs.


Manager NEM Real Time Operations

53335RECLASSIFY CONTINGENCY16/05/2016 11:43:18 PM

Reclassification of a Non-Credible Contingency Event: Rowville - Yallourn No.5 & No.6 220 kV Lines in Victoria due to Lightning.

AEMO ELECTRICITY MARKET NOTICE

Reclassification of a Non-Credible Contingency Event: Rowville - Yallourn No.5 & No.6 220 kV Lines in Victoria due to Lightning.

Lightning is occurring near the Rowville - Yallourn No.5 & No.6 220 kV Lines.

AEMO considers the simultaneous trip of those circuits to now be more likely.

Therefore AEMO has reclassified this as a credible contingency event from 2345hrs 16 May 2016 until further notice.

Constraint Set

V-ROYP56_R_N-2 invoked.


Manager NEM Real Time Operations