Update - Reclassification of a Non-Credible Contingency Event in TAS Region
Update - Reclassification of a Non-Credible Contingency Event in TAS Region:
Trip of any Tasmanian Transmission Line and Basslink Interconnector for Basslink flow in the direction of Victoria to Tasmania
Refer to MN 47360 issued 19/12/2014 and MN 47855 issued 23/01/2015.
Advice provided to AEMO indicates that Basslink is unlikely to trip for 220 kV transmission faults close to George Town. As the George Town to Tamar Valley power station 220 kV lines are very short it is unlikely that Basslink will trip for a fault on these lines.
Based on this advice AEMO has reclassified the loss of any transmission line in Tasmania and Basslink Interconnector to be a credible contingency event for Basslink flow in the direction of Victoria to Tasmania only, except for faults on either of the two George Town to Pacific Aluminium 220 kV transmission lines or the George Town to Tamar Valley power station 220 kV transmission line, from 1151 hrs 13/06/2016 until further notice.
Manager NEM Real Time Operations
Reclassification of the loss of Wagga 132kV B bus, No2 and No3 transformer as a credible event 11 June 2016
Refer AEMO ELECTRICITY MARKET NOTICE 53874
At 0950 hrs on 11/06/16, the Wagga substation 132kV B bus, the No2 and the No3 330/132kV transformers tripped.
The cause of this non credible contingency event is not known at this stage.
AEMO is not satisfied that this non credible event is unlikely to re-occur.
AEMO therefore classifies this event as being a credible contingency event.
The No3 330/132kV transformer and the bus were placed on load from 1430hrs, the No2 330/132kV transformer remains de-energised.
Manager NEM Real Time Operations
Cancellation of the Reclassification of a Non-Credible Contingency Event: Bouldercombe - Rockhampton 7108 and Bouldercombe - Egans Hill 7221 132 kV Lines in Queensland due to Lightning.
Cancellation of the Reclassification of a Non-Credible Contingency Event: Bouldercombe - Rockhampton 7108 and Bouldercombe - Egans Hill 7221 132 kV Lines in Queensland due to Lightning.
Refer to AEMO Electricity Market Notice no. 53614
There is no longer any Lightning activity in the vicinity of the Bouldercombe - Rockhampton 7108 and Bouldercombe - Egans Hill 7221 132 kV Lines.
AEMO has cancelled the reclassification of the simultaneous trip of those circuits as a credible contingency event at 0235 hrs.
Manager NEM Real Time Operations
Cancellation of the Reclassification of a Non-Credible Contingency Event: Collinsville North - Mackay Tee Proserpine 7125 and 7126 132 kV Lines in Queensland due to Lightning.
Cancellation of the Reclassification of a Non-Credible Contingency Event: Collinsville North - Mackay Tee Proserpine 7125 and 7126 132 kV Lines in Queensland due to Lightning.
Refer AEMO Electricity Market Notice 53607
There is no longer any lightning activity in the vicinity of the Collinsville North - Mackay Tee Proserpine 7125 and 7126 132 kV Lines.
AEMO has cancelled the reclassification of the simultaneous trip of those circuits as a credible contingency event at 0150 hrs.
Manager NEM Real Time Operations
Cancellation of the Reclassification of a Non-Credible Contingency Event: Collinsville - Stoney Ck 7306 and Collinsville - Newlands 7121 132 kV Lines in Qld Region due to Lightning.
Cancellation of the Reclassification of a Non-Credible Contingency Event: Collinsville - Stoney Ck 7306 and Collinsville - Newlands 7121 132 kV Lines in Qld Region due to Lightning.
Refer to AEMO Electricity Market Notice 53604
There is no longer any lightning activity in the vicinity of the Collinsville - Stoney Ck 7306 and Collinsville - Newlands 7121 132 kV Lines
AEMO has cancelled the reclassification of the simultaneous trip of those circuits as a credible contingency event from 0120 hrs.
Manager NEM Real Time Operations
Reclassification of a Non-Credible Contingency Event: Bouldercombe - Rockhampton 7108 and Bouldercombe - Egans Hill 7221 132 kV Lines in Queensland due to Lightning.
Reclassification of a Non-Credible Contingency Event: Bouldercombe - Rockhampton 7108 and Bouldercombe - Egans Hill 7221 132 kV Lines in Queensland due to Lightning.
Lightning is occurring near the Bouldercombe - Rockhampton 7108 and Bouldercombe - Egans Hill 7221 132 kV Lines.
AEMO considers the simultaneous trip of those circuits to now be more likely.
Therefore AEMO has reclassified this as a credible contingency event from 0005 hrs 04/06/16 until further notice.
Manager NEM Real Time Operations
Cancellation of the Reclassification of a Non-Credible Contingency Event: Kemmis - Moranbah Tee Burton Downs 7117 and Nebo - Moranbah Tee Coppabella 7118 132 kV Lines in Queensland due to Lightning
Cancellation of the Reclassification of a Non-Credible Contingency Event: Kemmis - Moranbah Tee Burton Downs 7117 and Nebo - Moranbah Tee Coppabella 7118 132 kV Lines in Queensland due to Lightning.
Refer to AEMO Electricity Market Notice no. 53606
There is no longer any Lightning occurring near the Kemmis - Moranbah Tee Burton Downs 7117 and Nebo - Moranbah Tee Coppabella 7118 132 kV Lines.
AEMO has cancelled the reclassified this as a credible contingency event at 2355 hrs
Manager NEM Real Time Operations
Cancellation of the Reclassification of a Non-Credible Contingency Event: Moranbah - Goonyella 7369 and 7370 132 kV Lines in Queensland due to Lightning.
Cancellation of the Reclassification of a Non-Credible Contingency Event: Moranbah - Goonyella 7369 and 7370 132 kV Lines in Queensland due to Lightning.
Refer AEMO Electricity Market Notice 53605
There is no longer any lightning activity in the vicinity of the Moranbah - Goonyella 7369 and 7370 132 kV Lines.
AEMO has cancelled the reclassification of the simultaneous trip of those circuits as a credible contingency event at 2345 hrs.
Manager NEM Real Time Operations
Reclassification of a Non-Credible Contingency Event: Collinsville North - Mackay Tee Proserpine 7125 and 7126 132 kV Lines in Queensland due to Lightning.
Reclassification of a Non-Credible Contingency Event: Collinsville North - Mackay Tee Proserpine 7125 and 7126 132 kV Lines in Queensland due to Lightning.
Lightning is occurring near the Collinsville North - Mackay Tee Proserpine 7125 and 7126 132 kV Lines.
AEMO considers the simultaneous trip of those circuits to now be more likely.
Therefore AEMO has reclassified this as a credible contingency event from 2130 hrs 03/06/16 until further notice.
Manager NEM Real Time Operations