Market Notices

54162INTER-REGIONAL TRANSFER28/06/2016 05:14:30 PM

Update on Heywood Interconnector upgrade

AEMO ELECTRICITY MARKET NOTICE

Update on Heywood Interconnector upgrade

Refer to Market Notice 51916

ElectraNet expects to achieve commercial operation of the South East - Tailem Bend 275 kV line series compensation by 31 July 2016. At this time, capability of the Heywood interconnector will be 570 MW for transfer from Victoria to South Australia and 500 MW for transfer from South Australia to Victoria. Further transfer capability will be released subject to completion of inter-network testing to prove system performance and validate system models. System conditions for the conduct of these tests are being obtained through normal market dispatch.

Based on progress with the testing to date, full capability for transfer from Victoria to South Australia is likely to be achieved by February 2017. However, it appears unlikely that the market will deliver sufficient test conditions to enable achievement of full capability for transfer from South Australia to Victoria before March 2017.
If the full range of required conditions are not obtained by July 2017, AEMO and ElectraNet may seek to obtain test facilitation services in order to complete the inter-network tests. This will allow the market approximately 12 months to deliver the required test conditions from when the South East - Tailem Bend series compensation is commissioned.

The inter-network test program for the Heywood interconnector upgrade provides further information and is published on AEMO's website at the following link:
http://www.aemo.com.au/Consultations/National-Electricity-Market/Heywood-interconnector-upgrade-program-for-internetwork-tests

AEMO Operations
54159RESERVE NOTICE28/06/2016 03:05:10 PM

Forecast Lack Of Reserve Level 1 (LOR1) in the South Australia region - STPASA - 4-5 July 2016

AEMO ELECTRICITY MARKET NOTICE

AEMO declares a Forecast LOR1 condition for the South Australia region for the following period(s):

1. From 04/07/2016 1230 hrs to 2300 hrs
The contingency capacity reserve required is 400 MW
The minimum reserve available is 247 MW

2. From 04/07/2016 2330 hrs to 05/07/2016 0030 hrs
The contingency capacity reserve required is 400 MW
The minimum reserve available is 281 MW

3. From 05/07/2016 1800 hrs to 2030 hrs
The contingency capacity reserve required is 400 MW
The minimum reserve available is 285 MW

Harmohan Singh
Operations Planning
54140INTER-REGIONAL TRANSFER26/06/2016 06:05:06 AM

Inter-regional transfer limit variation - Horsham-Waubra 220 kV Transmission Line (Vic)

AEMO ELECTRICITY MARKET NOTICE

Inter-regional transfer limit variation - Horsham-Waubra 220 kV Transmission Line (Vic)

The planned outage of the Horsham-Waubra 220 kV Line starting at 0600 hrs has been cancelled.

The following constraint set was associated with this outage.
V-HOWA

The constraint set contains equations with the following interconnectors on the LHS.

NSW-QLD1
VIC1-NSW1
V-SA
V-S-MNSP1
T-V-MNSP1

Manager NEM Real Time Operations
54135INTER-REGIONAL TRANSFER25/06/2016 11:32:10 PM

Inter-regional transfer limit variation Lismore SVC - NSW Saturday, 25 June 2016

AEMO ELECTRICITY MARKET NOTICE

Inter-regional transfer limit variation Lismore SVC - NSW Saturday, 25 June 2016

At 2320 hrs, there was an unplanned outage of the Lismore SVC.

The following constraint set was invoked from 2325 hrs.
N-LS_VC1

The constraint set contains equations with the following interconnectors on the LHS.

N-Q-MNSP1
NSW1_QLD1


See Network Outage Scheduler (NOS) for further details

Manager NEM Real Time Operations
54132INTER-REGIONAL TRANSFER25/06/2016 08:43:58 AM

Inter-regional transfer limit variation - Liverpool - Sydney West No. 30 330 kV Transmission Line (NSW)

AEMO ELECTRICITY MARKET NOTICE

Inter-regional transfer limit variation - Liverpool - Sydney West No. 30 330 kV Transmission Line (NSW)

Liverpool - Sydney West No. 30 330 kV Transmission Line has been returned to service early in the NSW region.

The following constraint set was revoked at 0845 hrs.
N-LPSW_30

The constraint set contains equations with the following interconnectors on the LHS.
N-Q-MNSP1
NSW-QLD1
VIC1-NSW1

Refer to AEMO Network Outage Schedule for further details.

Manager NEM Real Time Operations
54124INTER-REGIONAL TRANSFER24/06/2016 11:07:26 AM

Inter-Regional Transfer limit variation - APD to Heywood No.1 500kV line (Vic Region) - 24/06/16.

AEMO ELECTRICITY MARKET NOTICE

Inter-Regional Transfer limit variation - APD to Heywood No.1 500kV line (Vic Region) 24/06/16.

There is a short notice outage of APD - Heywood No.1 500kV line.

The following Constraint Set was invoked from 1050 hrs.

V-APHY1_2


This Constraint Set contain equations with the following interconnectors on the LHS

V-SA


Refer to AEMO Network Outage Schedule for further details.

Manager NEM Real Time Operations
54112INTER-REGIONAL TRANSFER23/06/2016 05:51:52 PM

Cancellation Inter-Regional Transfer limit variation: Basslink

AEMO ELECTRICITY MARKET NOTICE

Cancellation Inter-Regional Transfer limit variation: Basslink
At 1730 hrs on the 23 June 2016 the Basslink interconnector was returned to service.
Constraint set I-BL_ZERO revoked

Manager NEM Real Time Operations
54064INTER-REGIONAL TRANSFER23/06/2016 05:54:29 AM

Cancellation - Inter-Regional transfer limit variation Murraylink - Thursday, 23 June 2016.

AEMO ELECTRICITY MARKET NOTICE


Cancellation - Inter-Regional transfer limit variation Murraylink - Thursday, 23 June 2016.

Refer Market Notice 54063

Murraylink has been returned to service at 0544 hrs

Constraint set I-ML_ZERO revoked at 0550 hrs

The constraint set has the following interconnector on the LHS.

V-S-MNSP1


Manager NEM Real Time Operations

54063INTER-REGIONAL TRANSFER23/06/2016 04:12:50 AM

Inter-regional transfer limit variation - Murraylink, Thursday, 23 June 2016

AEMO ELECTRICITY MARKET NOTICE

Inter-regional transfer limit variation - Murraylink, Thursday, 23 June 2016

At 0404 hrs there was an unplanned outage of Murraylink.

The following constraint set was invoked at 0410 hrs until further notice.

I-ML_ZERO

The constraint set contains equations with the following interconnectors on the LHS.

V-S-MNSP1


Manager NEM Real Time Operations