Market Notices

53436INTER-REGIONAL TRANSFER20/05/2016 02:15:07 AM

Inter-regional transfer limit variation for Transient Stability Limit - Vic Region - 20 May 2016

AEMO ELECTRICITY MARKET NOTICE

Inter-regional transfer limit variation for Transient Stability Limit - Vic Region - 20 May 2016

The AEMO Dynamic Stability Analysis application is indicating violations for a fault on a Hazelwood - South Morang 500 kV transmission line in the Victoria region.

The following constraints have been invoked to apply offset reductions to the Victoria transient stability export limit.

Constraint V-DSA_STAB-050 invoked from 0215 hrs until further notice

Constraints have the following interconnectors on the LHS
NSW1-QLD1
T-V-MNSP1
V-S-MNSP1
V-SA
VIC1-NSW1

Manager NEM Real Time Operations
53435INTER-REGIONAL TRANSFER20/05/2016 01:15:07 AM

Inter-regional transfer limit variation - Tarong to South Pine (832) 275kV Line (Qld) - Voltage Control - 20 May 2016

AEMO ELECTRICITY MARKET NOTICE

Inter-regional transfer limit variation - Tarong to South Pine (832) 275kV Line (Qld) - Voltage Control - 20 May 2016

The Tarong to South Pine (832) 275kV Line has been de-energised to manage voltages in the Qld region.

The following constraint set was invoked at 0115 hrs until further notice.

Q-TRSP_832

The constraint set contains equations with the following interconnectors on the LHS.

N-Q-MNSP1


Manager NEM Real Time Operations
53401INTER-REGIONAL TRANSFER18/05/2016 05:14:33 AM

Cancellation -Inter-regional transfer limit variation - Tarong to South Pine (832) 275kV Line (Qld) - Voltage Control

AEMO ELECTRICITY MARKET NOTICE

Cancellation -Inter-regional transfer limit variation - Tarong to South Pine (832) 275kV Line (Qld) - Voltage Control - 18 May 2016

Refer MN 53400

The Tarong to South Pine (832) 275kV Line has been returned to service.

The following constraint set was revoked at 0540 hrs..

Q-TRSP_832

The constraint set contains equations with the following interconnectors on the LHS.

N-Q-MNSP1


Manager NEM Real Time Operations
53400INTER-REGIONAL TRANSFER18/05/2016 03:03:57 AM

Inter-regional transfer limit variation - Tarong to South Pine (832) 275kV Line (Qld) - Voltage Control - 18 May 2016

AEMO ELECTRICITY MARKET NOTICE

Inter-regional transfer limit variation - Tarong to South Pine (832) 275kV Line (Qld) - Voltage Control - 18 May 2016

The Tarong to South Pine (832) 275kV Line has been de-energised to manage voltages in the Qld region.

The following constraint set was invoked at 0310 hrs until further notice.

Q-TRSP_832

The constraint set contains equations with the following interconnectors on the LHS.

N-Q-MNSP1


Manager NEM Real Time Operations
53399INTER-REGIONAL TRANSFER17/05/2016 02:57:25 PM

Inter-Regional Transfer Limit Variation - Directlink - NSW Region 17 May 2016

AEMO ELECTRICITY MARKET NOTICE

Inter-Regional Transfer Limit Variation - Directlink - NSW Region - 17 May 2016

The planned outage of the DC2 pole of Directlink was scheduled to complete at 1700 hrs 18/05/16.

The outage has completed early

The following constraint set for this outage was revoked at 1455 hrs.
N-X_MBTE_2

The constraint set contains the following interconnector on the left hand side:
N-Q-MNSP1

See AEMO Network Outage Scheduler (NOS) for further details.

Manager NEM Real Time Operations
53317INTER-REGIONAL TRANSFER16/05/2016 05:32:36 AM

Cancellation - Inter-regional Inter-regional transfer limit variation - Greenbank to Middle Ridge (8849) 275kV Line (Qld) - Voltage Control

AEMO ELECTRICITY MARKET NOTICE

Cancellation - Inter-regional transfer limit variation - Greenbank to Middle Ridge (8849) 275kV Line (Qld) - Voltage Control - Monday, 16 May 2016

Refer to MN 53307

The Greenbank to Middle Ridge (8849) 275kV Line was returned to service.

The following constraint set was revoked at 0530 hrs until further notice.

Q-MRGB_8848_8849

The constraint set contains equations with the following interconnectors on the LHS.

NSW-QLD1
N-Q-MNSP1


Manager NEM Real Time Operations
53316INTER-REGIONAL TRANSFER16/05/2016 05:20:49 AM

Cancellation -Inter-regional transfer limit variation - Tarong to South Pine (832) 275kV Line (Qld) - Voltage Control

AEMO ELECTRICITY MARKET NOTICE

Cancellation -Inter-regional transfer limit variation - Tarong to South Pine (832) 275kV Line (Qld) - Voltage Control - Monday, 16 May 2016

Refer MN 53308

The Tarong to South Pine (832) 275kV Line has been returned to service.

The following constraint set was revoked at 0520 hrs..

Q-TRSP_832

The constraint set contains equations with the following interconnectors on the LHS.

N-Q-MNSP1


Manager NEM Real Time Operations
53308INTER-REGIONAL TRANSFER16/05/2016 01:19:54 AM

Inter-regional transfer limit variation - Tarong to South Pine (832) 275kV Line (Qld) - Voltage Control

AEMO ELECTRICITY MARKET NOTICE

Inter-regional transfer limit variation - Tarong to South Pine (832) 275kV Line (Qld) - Voltage Control - Monday, 16 May 2016

The Tarong to South Pine (832) 275kV Line has been de-energised to manage voltages in the Qld region.

The following constraint set was invoked at 0120 hrs until further notice.

Q-TRSP_832

The constraint set contains equations with the following interconnectors on the LHS.

N-Q-MNSP1


Manager NEM Real Time Operations
53307INTER-REGIONAL TRANSFER16/05/2016 12:18:49 AM

Inter-regional Inter-regional transfer limit variation - Greenbank to Middle Ridge (8849) 275kV Line (Qld) - Voltage Control

AEMO ELECTRICITY MARKET NOTICE

Inter-regional transfer limit variation - Greenbank to Middle Ridge (8849) 275kV Line (Qld) - Voltage Control - Monday, 16 May 2016

The Greenbank to Middle Ridge (8849) 275kV Line has been de-energised to manage voltages in the Qld region.

The following constraint set was invoked at 0015 hrs until further notice.

Q-MRGB_8848_8849

The constraint set contains equations with the following interconnectors on the LHS.

NSW-QLD1
N-Q-MNSP1



Manager NEM Real Time Operations