Planned outage of Heywood No.1 500kV Bus in Victoria region from 10/08/2016 0700 hrs to 12/08/2016 1700 hrs
This market notice is FOR INFORMATION ONLY.
The Heywood No.1 500 kV busbar in Victoria Region is planned out of service from 0700 hrs on 10 August 2016 to 1700 hrs on 12 August 2016. During this outage, Heywood 500/275 kV M1 transformer will be off-loaded and Heywood - Tarrone - Alcoa Portland No.1 500 kV line will be open at Heywood.
During this outage, a credible contingency can separate South Australia region from the rest of the NEM.
Under these circumstances, 35 MW of Raise and Lower regulation FCAS will be sourced from South Australia for the duration of this outage. In addition, consistent with AEMO existing procedures, adequate contingency FCAS lower requirements will also be sourced from South Australia at times when power transfer is from South Australia to Victoria.
The following constraint sets have been invoked for this outage:
F-I_HYSE (includes F-S_LREG_0035 and F-S_RREG_0035)
S-BOTH_BLKRG_C_OS
V-HYTX_M12
V-HY_500BUS
Refer AEMO Network Outage Schedule (NOS) for further details.
AEMO will continue monitoring this proposed outage and will update the Market accordingly.
Operations Planning
Update - AEMO Brisbane Control Room evacuated - Saturday, 16 July 16
Refer to AEMO Electricity Market Notice no. 54522
AEMO advises all participants that as of 1435 hrs 16 July 2016, the AEMO Brisbane Control Centre site is now occupied.
All operational communications will now revert back to normal
Manager NEM Real Time Operations
AEMO Brisbane control room evacuated - Saturday, 16 July 2016
AEMO Brisbane control room evacuated - Saturday, 16 July 2016
AEMO advises all participants that as of 1416 hrs Saturday, 16 July 2016 the AEMO Brisbane site has been evacuated.
Until further notice all operational matters will be handled by the Sydney Control Centre
Manager NEM Real Time Operations
Network Augmentation De-commissioned - QLD Region - 15/07/16
Network Augmentation De-commissioned - QLD Region - 15/07/16
The following transmission equipment in the Queensland region has been de-commissioned.
Mackay - Proserpine 7215/2 132 kV Line.
Manager NEM Real Time Operations
Network Augmentation De-commissioned - South Australia Region - 15/07/16
Network Augmentation De-commissioned - South Australia Region - 15/07/16
The following transmission equipment in the South Australia region has been de-commissioned.
Keith - Tailem Bend No. 1 132 kV Line
Keith - Snuggery 132 kV Line
Manager NEM Real Time Operations
Planned outage of Tailem Bend 275kV - South East 275kV No.2 line from 16/07/2016 0745 hrs to 24/07/2016 1730hrs
?
During this outage, South Australia (SA) will remain connected to the NEM via the Tailem Bend - South East No.1 275kV line and the 132kV network.
?
A trip of the Tailem Bend - South East No. 1 275kV line will sever the 275 kV connections between the NEM and SA. SA will remain connected to the NEM via the 132kV network, which if it remains in service will pose a system security issue.
?
In the event of a trip of the Tailem Bend - South East No. 1 275kV line, AEMO will invoke FCAS regulation constraint sets F-S_LREG_0035 and F-S_RREG_0035
?
In addition,? AEMO will take all necessary steps as outlined in Section 6.1 of SO-OP-3715 Power System Security Guideline to separate the 132kV network and therefore manage an orderly separation of SA from the NEM.?
?
?
Operations Planning
Cancellation of the Forecast Lack Of Reserve Level 2 (LOR2) condition in the South Australia region - STPASA
The Forecast LOR2 conditions in the South Australia region advised in AEMO Electricity Market Notice No. 54410 are cancelled at 1200 hrs 12/07/2016.
Ashley Dunn
Operations Planning
FORECAST LACK OF RESERVE LEVEL 2 (LOR2) in the South Australia region (ST PASA).
AEMO ELECTRICITY MARKET NOTICE
FORECAST LACK OF RESERVE LEVEL 2 (LOR2) in the South Australia region (ST PASA).
AEMO declares forecast LOR2 conditions for the South Australia region for the following periods.
Wednesday 13th July 2016 from 1800 hrs to 1830 hrs
The minimum reserve available is 163 MW.
Thursday 14th July 2016 from 1830 hrs to 1930 hrs
The minimum reserve available is 171 MW.
This calculation is based on a LOR2 trigger level of 200 MW.
AEMO is seeking a market response.
Manager NEM Real Time Operations
Cancellation - Forecast Lack Of Reserve Level 2 (LOR2) in the SA Region - PDPASA - 7 Jul 2016
Cancellation - Forecast Lack Of Reserve Level 2 (LOR2) in the SA Region - PDPASA - 7 Jul 2016
The Forecast LOR2 condition in the SA Region advised in AEMO Electricity Market Notice No. 54303 is cancelled at 1920 hrs 7 Jul 2016.