Market Notices

91571INTER-REGIONAL TRANSFER09/10/2021 04:04:30 PM

Cancellation - Inter-regional transfer limit variation - constraint automation to manage Power System Security in NSW region - 09/10/2021

AEMO ELECTRICITY MARKET NOTICE

Cancellation - Inter-regional transfer limit variation - constraint automation to manage Power System Security in NSW region - 09/10/2021

Refer AEMO Electricity Market Notice 91562

Constraint set CA_BRIS_50737673 was revoked at 1600 hrs 9/10/21.

This constraint set contains equations with the following interconnector on the LHS;

VIC1-NSW1

Manager NEM Real Time Operations
91570RECLASSIFY CONTINGENCY09/10/2021 03:43:27 PM

Cancellation of the reclassification of a non-credible contingency event as a credible contingency event due to lightning.

AEMO ELECTRICITY MARKET NOTICE.

Cancellation of the reclassification of a non-credible contingency event as a credible contingency event due to lightning.

AEMO considers the simultaneous trip of the following circuits is no longer reasonably possible. There is no longer any lightning activity in the vicinity of the following lines. Accordingly its classification has reverted to a non-credible contingency event.

Region: TAS

Lines: Farrell - Sheffield No. 1 and No. 2 220kV lines

Cancellation time: 09/10/2021 1534 hrs
Constraint set(s) revoked:

F-T-FASH_N-2
T-FASH_N-2_CP4_S1
T-NIL_WCP_CLOSE

Refer AEMO Electricity Market Notice 91563

Manager NEM Real Time Operations
91569RESERVE NOTICE09/10/2021 03:17:45 PM

STPASA - Forecast Lack Of Reserve Level 1 (LOR1) in the QLD Region on 14/10/2021

AEMO ELECTRICITY MARKET NOTICE

AEMO declares a Forecast LOR1 condition under clause 4.8.4(b) of the National Electricity Rules for the QLD region for the following period:

[1.] From 1830 hrs 14/10/2021 to 1900 hrs 14/10/2021.
The forecast capacity reserve requirement is 1163 MW.
The minimum capacity reserve available is 1140 MW.


Manager NEM Real Time Operations
91563RECLASSIFY CONTINGENCY09/10/2021 01:10:35 PM

Reclassification of a Non-Credible Contingency Event: Farrell - Sheffield No. 1 and No. 2 220kV lines in TAS due to lightning.

AEMO ELECTRICITY MARKET NOTICE.

Reclassification of a non-credible contingency event as a credible contingency event due to lightning.

AEMO considers the simultaneous trip of the following circuits to now be more likely and reasonably possible. Accordingly AEMO has reclassified it as a credible contingency event.

Region: TAS

Lines: Farrell - Sheffield No. 1 and No. 2 220kV lines

Duration: 09/10/2021 13:04 hrs until further notice

Constraint set(s) invoked:

F-T-FASH_N-2
T-FASH_N-2_CP4_S1
T-NIL_WCP_CLOSE

Manager NEM Real Time Operations
91562INTER-REGIONAL TRANSFER09/10/2021 11:09:09 AM

Inter-regional transfer limit variation - constraint automation to manage Power System Security in NSW region - 09/10/2021

AEMO ELECTRICITY MARKET NOTICE

Inter-regional transfer limit variation - constraint automation to manage Power System Security in NSW region - 09/10/2021

In order to maintain the power system in a secure operating state in the NSW region, AEMO has invoked automated constraint set CA_BRIS_50737673 from 1100 hrs until further notice.

This constraint set contains equations with the following interconnector on the LHS;

VIC1-NSW1

Manager NEM Real Time Operations
91560MARKET SYSTEMS08/10/2021 04:23:11 PM

CHG0070490 | Pre-Production | This outage is to allow the deployment of a 5MS Defect release for MSATS and eEMDM to Pre-Production. MSATS will be unavailable

Change Number: CHG0070490
Notification issued to: Market Notice

Notification Type: Initial
Change Type: Normal

Service/ Component:
MSATS - Consumer Administration and Transfer Solution(CATS)

Change Title: This outage is to allow the deployment of a 5MS Defect release for MSATS and eEMDM to Pre-Production. MSATS will be unavailable during this outage period.

Change Start Date & Time: 12/10/2021 18:00:00 AEST
Change End Date & Time: 13/10/2021 16:00:00 AEST
Outage Start Date & Time: 12/10/2021 18:00:00 AEST
Outage End Date & Time: 12/10/2021 20:00:00 AEST

Environment: Pre-Production

Participant Impact and Requirements: There will be no access to the Pre-Production MSATS system for the duration of the outage. Please access outside these hours.

Support Information:
Report any impacts to the AEMO Information and Support Hub or call 1300 236 600.

Please refer to:
https://aemo.service-now.com/participantportal?id=pp_services_status for any planned/unplanned maintenance activities.
91557RESERVE NOTICE08/10/2021 02:29:51 PM

STPASA - Cancellation of the Forecast Lack Of Reserve Level 1 (LOR1) in the SA on 11/10/2021

AEMO ELECTRICITY MARKET NOTICE

The Forecast LOR1 condition in the SA region advised in AEMO Electricity Market Notice No. 91530 is cancelled at 1400 hrs 08/10/2021.

No LOR condition is currently forecast in the STPASA period.

AEMO Operations
91552MARKET SYSTEMS08/10/2021 09:32:25 AM

CHG0070448 | Completed | Pre-Production | This outage is to allow the deployment of a 5MS Defect release for MSATS and eEMDM to Pre-Production. . MSATS will be

Change Number: CHG0070448
Notification issued to: Market Notice
Notification Type: Completed
Change Type: Normal
Service/Component: MSATS - Consumer Administration and Transfer Solution(CATS)
Change Title: This outage is to allow the deployment of a 5MS Defect release for MSATS and eEMDM to Pre-Production. . MSATS will be unavailable during this outage period.
Support Information: Report any impacts to the AEMO Information and Support Hub or on External 1300 236 600.
91551MARKET INTERVENTION07/10/2021 08:49:07 PM

Possible intervention to manage power system security in South Australia (SA) Region

AEMO ELECTRICITY MARKET NOTICE

Possible intervention to manage power system security in South Australia (SA) Region

The synchronous generating units currently expected to be synchronised in SA from 2130 hrs 08/10/2021 to 0400 hrs 09/10/2021 will be inadequate to maintain sufficient system strength in SA and hence a secure operating state.

AEMO estimates that, in the absence of sufficient market response by 1730 hrs 08/10/2021, AEMO may need to intervene by issuing a direction requiring one or more SA synchronous generating unit(s) to operate or remain synchronised to maintain power system security in SA.

Manager NEM Real Time Operations
X
Cookies help us improve your website experience.
By using our website, you agree to our use of cookies.
Confirm