Market Notices

138260RESERVE NOTICE29/03/2026 12:56:01 PM

PDPASA - Forecast Lack Of Reserve Level 2 (LOR2) in the SA Region on 30/03/2026

AEMO ELECTRICITY MARKET NOTICE

AEMO declares a Forecast LOR2 condition under clause 4.8.4(b) of the National Electricity Rules for the SA region for the following Periods:


[1.] From 1800 hrs 30/03/2026 to 1830 hrs 30/03/2026.
The forecast capacity reserve requirement is 318 MW.
The minimum capacity reserve available is 286 MW.


[2.] From 1900 hrs 30/03/2026 to 1930 hrs 30/03/2026.
The forecast capacity reserve requirement is 311 MW.
The minimum capacity reserve available is 295 MW.


[3.] From 2000 hrs 30/03/2026 to 2030 hrs 30/03/2026.
The forecast capacity reserve requirement is 308 MW.
The minimum capacity reserve available is 301 MW.


AEMO is seeking a market response.

AEMO has not yet estimated the latest time at which it would need to intervene through an AEMO intervention event.


Manager NEM Real Time Operations
137916GENERAL NOTICE28/03/2026 03:16:56 PM

Planned outage of Broadsound - Stanwell No. 856 275 kV line in the QLD region beginning on 28/03/2026

AEMO ELECTRICITY MARKET NOTICE

The Broadsound - Stanwell No. 856 275 kV line in the Queensland (QLD) region is planned to be out of service from 1800 hrs 28/03/2026 to 2300 hrs 28/03/2026.

This outage is considered a High Impact Outage (HIO) as the outage recall is greater than 30 minutes.
A credible contingency event during this planned outage may require market intervention, such as the issuing of directions.

Refer AEMO Network Outage Schedule (NOS) for further details.

Manager NEM Real Time Operations
135916GENERAL NOTICE23/03/2026 10:29:33 AM

SERVICE INTERRUPTION - Partial SCADA failure NSW

AEMO ELECTRICITY MARKET NOTICE

SERVICE INTERRUPTION

AEMO is experiencing a service interruption relating to: Partial SCADA failure NSW


AEMO is working on restoring the service. AEMO Support Hub will provide updates as more information becomes available.

Dispatch of market targets via SCADA / AGC has failed. Affected participants are requested to enable their backup systems in order to receive dispatch targets and manually follow dispatch targets until further notice. Affected participants are requested to contact the AEMO Electricity Control Room if unable to follow their dispatch targets.

For further enquiries please contact the AEMO Support Hub
Phone: 1300236600 Opt1
Email: [email protected]

Manager NEM Real Time Operations
135475RESERVE NOTICE22/03/2026 10:14:07 AM

STPASA - Update of the suspect Lack Of Reserve Level 2 (LOR2) condition in the Qld Region on 24/03/2026

AEMO ELECTRICITY MARKET NOTICE

The suspect LOR2 condition advised in AEMO Electricity Market Notice No. 135427 has been reviewed.

AEMO considers this forecast LOR2 condition invalid.

No LOR2 condition is currently forecast for the Qld region.

Manager NEM Real Time Operation
135427RESERVE NOTICE22/03/2026 06:23:53 AM

STPASA - Suspect Lack Of Reserve Level 2 (LOR2) in the Qld Region on 24/03/2026

AEMO ELECTRICITY MARKET NOTICE

AEMO considers that there is a suspect Forecast LOR2 condition for the Qld region for the following period:

[1.] From 1630 hrs to 1730 hrs on 24/03/2026.

AEMO is currently investigating this LOR2 forecast condition to confirm whether it is valid.

Manager NEM Real Time Operations
135150GENERAL NOTICE20/03/2026 12:19:01 PM

Network Augmentation Commissioned - NSW Region - 20/03/2026

AEMO ELECTRICITY MARKET NOTICE

A network augmentation has been commissioned in the NSW region at 1052 hrs 20/03/2026 as follows:

Eraring - Eraring BESS No.2P 330 kV Transmission Line

Manager NEM Real Time Operations
134775RESERVE NOTICE13/03/2026 01:17:44 PM

PDPASA - Suspect Lack Of Reserve Level 2 (LOR2) in the Qld Region on 14/03/2026

AEMO ELECTRICITY MARKET NOTICE

AEMO considers that there is a suspect Forecast LOR2 condition for the Qld region for the following period:

[1.] From 0630 hrs to 0800 hrs on 14/03/2026.

AEMO is currently investigating this LOR2 forecast condition to confirm whether it is valid.

Manager NEM Real Time Operations
134573GENERAL NOTICE06/03/2026 07:35:39 AM

Fast Frequency Response Market - Local dispatch of Very Fast Contingency FCAS in QLD

AEMO ELECTRICITY MARKET NOTICE

Following a review of the operation of the Very Fast FCAS market, from 10th Mar 2026 AEMO will increase the cap on dispatch of Very Fast Contingency FCAS in the QLD region from 100 MW to 200 MW, during periods where islanding of the QLD region is considered credible.

No other changes to the dispatch of Very Fast FCAS or FCAS constraint equations will be made on this date.

For more information on the Fast Frequency Response (FFR) initiative, please visit:
https://www.aemo.com.au/initiatives/major-programs/fast-frequency-response

AEMO Operations
133946GENERAL NOTICE27/02/2026 03:20:04 PM

Update - Vulnerable lines in Qld region

AEMO ELECTRICITY MARKET NOTICE.

Update - Lightning vulnerable lines in Qld region

Refer to AEMO Electricity Market Notice 133798 and 133799

At 1650 hrs on 19/02/2026 the Goonyella - North Goonyella Tee - Stony Creek No. 7122 and Goonyella - Newlands No. 7155 132 kV lines tripped and auto reclosed.

The cause of the trip was identified as due to lightning.

In accordance with SO_OP_3715, AEMO now considers the Goonyella - North Goonyella Tee - Stony Creek No. 7122 and Goonyella - Newlands No. 7155 132 kV lines to be vulnerable with a category of probable due to lightning.

Manager NEM Real Time Operations