Market Notices

132709MINIMUM SYSTEM LOAD11/01/2026 03:28:49 PM

Cancellation of Actual Minimum System Load (MSL) MSL1 event in the SA Region on 11/01/2026.

AEMO ELECTRICITY MARKET NOTICE

Cancellation of Actual Minimum System Load (MSL) MSL1 event in the SA Region on 11/01/2026.

Cancellation - Actual MSL1- SA Region at 1530 hrs 11/01/2026.

Refer to Market Notice 132706 for MSL1.

Manager NEM Real Time Operations
132708RECLASSIFY CONTINGENCY11/01/2026 01:29:25 PM

Cancellation of a Non-Credible Contingency Event: Collinsville North - Proserpine No.7125 132 kV line and Collinsville North - Proserpine No.7126 132 kV line in QLD1 due to Lightning.

AEMO ELECTRICITY MARKET NOTICE

Cancellation of reclassification of a Non-Credible Contingency Event as a Credible Contingency Event due to Lightning. AEMO considers the simultaneous trip of the following circuits is no longer reasonably possible. There is no longer any lightning activity in the vicinity of the following lines. Accordingly its classification has reverted to a non-credible contingency event.

Region: QLD1

Lines: Collinsville North - Proserpine No.7125 132 kV and Collinsville North - Proserpine No.7126 132 kV

Cancellation time: 11/01/2026 13:29

Constraint set(s) revoked:
NONE

Refer AEMO Electricity Market Notice 132697

Auto-generated on behalf of Manager NEM Real Time Operations
132707MINIMUM SYSTEM LOAD11/01/2026 11:55:42 AM

Cancellation of ForecastMinimum System Load (MSL) MSL1 event in the VIC Region on 11/01/2026.

AEMO ELECTRICITY MARKET NOTICE

Cancellation of Forecast Minimum System Load (MSL) MSL1 event in the VIC Region on 11/01/2026.

Cancellation - ForecastMSL1- VIC Region at 1145 hrs 11/01/2026.

Refer to Market Notice 132693for MSL1.

Manager NEM Real Time Operations
132706MINIMUM SYSTEM LOAD11/01/2026 11:50:58 AM

Actual Minimum System Load MSL1 condition in the SA Region on 11/01/2026

AEMO ELECTRICITY MARKET NOTICE
Actual Minimum System Load MSL1 condition in the SA Region on 11/01/2026

Update to Market Notice 132699 - AEMO has detected that there is an elevated risk of insufficient demand to maintain a secure operating state in the SA on 11/01/2026.

Minimum demand is forecast to be -33 MW at 1330 hrs, and the advisory threshold is:
- MSL1 34 MW
- MSL2 -117 MW
- MSL3 -468 MW

The demand is below the MSL1 threshold. The actual MSL1 condition is forecast to exist until 1600 hrs.

Forecast demand refers to forecast Operational Demand that excludes contribution from Significant Non-Scheduled Generation: see definitions at https://aemo.com.au/energy-systems/electricity/national-electricity-market-nem/data-nem/operational-demand-data .

Manager NEM Real Time Operations
132705INTER-REGIONAL TRANSFER11/01/2026 11:29:53 AM

Cancellation - Inter-regional transfer limit variation - constraint automation to manage Power System Security in VIC region - 10/01/2026

AEMO ELECTRICITY MARKET NOTICE

In order to maintain the power system in a secure operating state in the VIC region, AEMO had invoked automated constraint set CA_BRIS_5873DCEF from 0500 hrs to 1135 hrs 11/01/2026.

This constraint set contains equations with the following interconnector on the LHS;

V-S-MNSP1,V-SA,VIC1-NSW1

Refer to AEMO Network Outage Scheduler (NOS) for further information.

Manager NEM Real Time Operations
132704INTER-REGIONAL TRANSFER11/01/2026 11:30:56 AM

Correction - Inter-regional transfer limit variation - Multiple outage, 8848 and 8849 (Greenbank to Middle Ridge) 275kV line O/S - QLD region - 11/01/2026

AEMO ELECTRICITY MARKET NOTICE

Correction to Market Notice 132701
Inter-regional transfer limit variation - 8848 and 8849 (Greenbank to Middle Ridge) 275kV line O/S - QLD region - 11/01/2026

At 1130 hrs 11/01/2026 there will be a short notice outage of 8848 and 8849 (Greenbank to Middle Ridge) 275kV lines.

The following constraint set(s) invoked at 11:30 hrs 11/01/2026
Q-MRGB_8848_8849
Q-X_MRGB_MRGB

This constraint set(s) contains equations with the following interconnectors on the LHS.
N-Q-MNSP1,NSW1-QLD1

Refer to the AEMO Network Outage Scheduler for further information.

Manager NEM Real Time Operations
132703RECLASSIFY CONTINGENCY11/01/2026 11:21:47 AM

Cancellation: Reclassification of non-credible contingency event due to existence of widespread abnormal condition - Dederang - Murray 330 kV Lines - Vic region.

AEMO ELECTRICITY MARKET NOTICE.

AEMO considers the occurrence of a non-credible contingency event due to the widespread abnormal conditions advised in AEMO Electricity Market Notice 132647 is no longer reasonably possible and accordingly its classification has reverted to non-credible.

Cancellation time: 1130 hrs 11/01/2026

Constraint set(s) revoked:
V-DDMS_N-2
V-DBUSS_L

Manager NEM Real Time Operations
132702RECLASSIFY CONTINGENCY11/01/2026 11:21:37 AM

Cancellation: Reclassification of non-credible contingency event due to existence of widespread abnormal condition - Dederang - Sth Morang 330 kV Lines - Vic region.

AEMO ELECTRICITY MARKET NOTICE.

AEMO considers the occurrence of a non-credible contingency event due to the widespread abnormal conditions advised in AEMO Electricity Market Notice 132612 is no longer reasonably possible and accordingly its classification has reverted to non-credible.
Cancellation time: 1130 hrs 11/01/2026

Constraint set(s) revoked:
V-DDSM_N-2

Manager NEM Real Time Operations
132701INTER-REGIONAL TRANSFER11/01/2026 11:19:47 AM

Inter-regional transfer limit variation - Multiple outage, 8848 and 8849 (Greenbank to Middle Ridge) 275kV line O/S - QLD region - 11/01/2026

AEMO ELECTRICITY MARKET NOTICE

Inter-regional transfer limit variation - 8848 and 8849 (Greenbank to Middle Ridge) 275kV line O/S - QLD region - 11/01/2026

At 1130 hrs 11/01/2026 there will be a short notice outage of 8848 and 8849 (Greenbank to Middle Ridge) 275kV lines.

The following constraint set(s) invoked at 0800 hrs 13/01/2026
Q-MRGB_8848_8849
Q-MRGB_8848_8849

This constraint set(s) contains equations with the following interconnectors on the LHS.
N-Q-MNSP1,NSW1-QLD1

Refer to the AEMO Network Outage Scheduler for further information.

Manager NEM Real Time Operations